Product Category Cassette
Product Range Compact Cassette range
Capacity 2.50kW Cooling 3.20kW Heating
Model Number AUTH09KVLA

Technical Specifications

Indoor unit AUTH09KVLA
Outdoor unit AOTH09KBTA
Operation Type Reverse Cycle
Power Source V/Ph/Hz 230 / 1 / 50
Cooling Capacity kW (Rated (Min - Max)) 2.50 (0.9 - 3.6)
Heating Capacity kW (Rated (Min - Max)) 3.20 (0.9 - 4.5)
Input Power Cooling kW (Rated (Max)) 0.56 (1.13)
Input Power Heating kW (Rated (Max)) 0.76 (1.68)
EER Cooling kW/kW 4.46
COP Heating kW/kW 4.21
Star Rating Cooling (0-10) (Hot / Average / Cold) 4 / 3.5 / 3.5
Star Rating Heating (0-10) (Hot / Average / Cold) 3.5 / 3 / 2.5
Total Cooling Seasonal Performance Factor Residential kW (Hot / Average / Cold) 5.804 / 5.126 / 5.179
Heating Seasonal Performance Factor Residential kW (Hot / Average / Cold) 5.064 / 4.575 / 4.108
Total Cooling Seasonal Performance Factor Commercial kW (Hot / Average / Cold) 6.273 / 6.243 / 6.595
Heating Seasonal Performance Factor Commercial kW (Hot / Average / Cold) 5.067 / 4.771 / 4.364
Running Current amps (Cooling / Heating) 3 / 4
Moisture Removal l/hr 0.7
Indoor Sound Pressure Cooling dBA (High / Quiet) 33 / 28
Indoor Sound Pressure Heating dBA (High / Quiet) 34 / 27
Outdoor Sound Pressure dBA (Cooling / Heating) 41 / 46
Outdoor Sound Power dBA 59
Air Circulation (Indoor - High Fan) Cooling l/sec 150
Air Circulation (Indoor - High Fan) Heating l/sec 150
Indoor Unit Dimensions mm (Height x Width x Depth) 245 x 570 x 570
Indoor Unit Weight kg 15.00
Outdoor Unit Dimensions mm (Height x Width x Depth) 542 x 799 x 290
Outdoor Unit Weight kg 32.00
Grill Dimensions mm (Height x Width x Depth) 49 x 620 x 620
Grill Weight kg 2.30
Piping Connects mm Ø (Liquid / Gas) 6.35 / 9.52
Pipe Length m (Max (Precharged)) 20 (15)
Max Height Difference m 15
Operation Range Cooling °CDB (Min to Max) -10 to 46
Operation Range Heating °CDB (Min to Max) -15 to 24
Refrigerant Type R32
Refrigerant Amount g 850

Dimensions

What’s included in your purchase

AUTH09KVLA

Indoor Unit

AOTH09KBTA

Outdoor Unit

UTG-UFYF-W

Grill

AR-REJ1E

Wireless Remote Controller

Optional Parts

UTY-NXT-BOX

WiFi Control

UTY-RVRY

Wired Remote Controller - KAGAMI Controller

Key features

Easy installation and compact design. These compact cassette models are extremely discreet with a non-intrusive grille design that sits level with the ceiling. Air can be distributed throughout the space in up to four directions.

  • All DC
    All DC

    With All DC, electricity loss is decreased and power consumption reduced.

  • Auto Restart
    Auto Restart

    Should there be a temporary loss of power, the unit will automatically restart itself in the same operating mode, once the power is restored.

  • Auto Changeover
    Auto Changeover

    The unit automatically switches between operating modes based on the temperature setting and room temperature.

  • Automatic Air Flow Adjustment
    Automatic Air Flow Adjustment

    The micro-processor automatically adjusts the air flow to follow changes in room temperature.

  • Automatic Louvre
    Automatic Louvre

    The position of the louvres is set automatically to match the operating mode. It is also possible to adjust the louvres using the remote control.

  • Blue Fin Heat Exchanger
    Blue Fin Heat Exchanger

    Corrosion-resistance of the heat exchanger in coastal areas has been improved by blue fin treatment of the outdoor unit heat exchanger.

  • Economy Mode
    Economy Mode

    Limits the maximum operation current, and performs operation with the power consumption suppressed.

  • Filter Sign
    Filter Sign

    Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room.

  • i-PAM
    i-PAM

    i-PAM inverter technology enables high output and high efficiency performance.

  • ON-OFF Timer
    On-Off Timer

    ON-OFF timer can be set to operate once every 24 hours.

  • Program Timer
    Program Timer

    This timer allows selection of one of four options. ON, OFF, ON ––> OFF, or OFF ––> ON.

  • Removable Intake Grill
    Removable Intake Grill

    The indoor unit’s intake grille can be removed for easy cleaning and maintenance.

  • Sleep Timer
    Sleep Timer

    The micro-processor gradually changes the room temperature, allowing you to sleep comfortably at night.

  • Super Quiet Mode
    Super Quiet Mode

    The indoor units fan can operate at a low speed to produce quieter operation.

  • Up Down Swing
    Up/Down Swing Louvre

    The up/down louvre automatically swings up and down.

  • v-PAM
    V-PAM

    v-PAM inverter technology increases the maximum output of the compressor significantly and enables high power and high efficiency.

  • Washable Panel
    Washable Panel

    Dust that accumulates on the air conditioner can be easily cleaned with a damp cloth.

  • Automatic Fan Speed Adjustment

  • 10 Degree Heat
    10°C Heat Operation

    The room temperature can be set to go no lower than 10°C, thus ensuring that the room does not get too cold when not occupied.

Operating Manual

Click on the Download button below to get the pdf

Download PDF

This product is part of the Residential and Commercial Compact Cassette range

Back to Residential Compact Cassette range Back to Commercial Compact Cassette range
Get a Fujitsu Air Conditioner

Get a Quote

Find where to buy a Fujitsu General Heat Pump / Air Conditioner

map-icon-white Find a Stockist